The red LED
(T54) shows
the
radio module initialization, the connection attempts to the GSM
network and any traffic with if the SIM card is
working. You can start
sending [commands] after 30s or when LED (T41) will
flash at 1 second rate, green when standby and red when alarm function
A On or O+.
The yellow LED
(T28) shows the grid power when the adapter is used.
The
following examples below shows commands sent to the
controller as [BOLD] and
messages sent from the controller to the cell phone in GREEN. Status replies are
sent
to
any number sending request [Pw s]
[Pw ss] or to number
N1 in
list when calling number is not recognized. The system can be setup to
automatically send daily or repetitive status messages. see therfore
H?.
S General
status informations.
[Pw s] to the controller will
make it reply with
the current basic status.
R2 Off
Jn
Jn (Jn
eventual Junctions). See (J?).
R3 Off
Jn
(Items can
be removed from status(R4?).
R5
ON Jn
See or send [Pw
R?] for relais info's.
V1 13.5
Internal Bat Volt(T31) PowSupply
input.
V2 53.5
External Voltmeter(Terminal
33)0-150V.
T1 18.2
Temperature T1 (0-95) on Terminal 39.
T2
-24.2
Temperature Thermometer 2 (-40-125)
AC=1
RST
1
or 0 Grid (T29), 3Ph control.
G 24%
Tank (liquid)
level.
Y 56%
Hygrometer (0-100rH).
i0-7:
01101100 Inputs
Level.
A=ON M0
Alarm On/Off, Mic
On/Off, Status on call.
13:45
Controller time clock (RTC)
Items
can be
added or
removed from the basic
SMS status message. So command [V1-]
will remove line V1. V2- T1- T2- GL- and Yg- can also remove
corresponding line from the basic status message. Command [V1+] will make line V1 to be listed
again. Same for others...
[Pw ss] to the controller will send
back the current status from line V1.
V1
12.6
V2
60.2
T1
22.2
T2
20.8
AC=1
0ST Grid,
only phases 2,3.
G
50.1% Level
sensor
Y
53.3% Humidity
sensor
Cd
11:23 Run
time counter. DAY form
00:00
CT
1982:13 Run
time counter TOTAL
Pd
240 Pulses
counter. DAY form
00:00
PT
2354148 Pulses
counter TOTAL
i0-7:
10111111
A=ON
M0
11:23
A Alarm
Inputs.
Display Alarm Delays.
Force Alarm.
Up to six alarm inputs can be connected. The sensor (or group of
sensors) can
be any (magnet, pressure, temp, …) switch contacts directly connected
to
the controller inputs. Any device, like motion detectors or fire alarm
sensors
with a potential free output
that can make or break a circuit (between
GND and
the input), like a switch will do, can be used.
Be sure that no voltage
(or in any cases no more as +12Vdc) will be applied on the inputs. In
fact, circuit shorted to GND or open is enough to make the input
trigger an alarm (or a Junction event, see J?) and is the way that
should be used to drive the inputs A0 to A7.
Inputs 0-7 High level (circuit open) should show about 3.3V and can not drive out
any current!
Any level CHANGE on Inputs
A1 to A7 will trigger the alarm and the
emission of
an Alarm SMS after a corresponding Input Delay. Several SMS can be sent
according to parameter D [Pw D?]
starting from N1 of the number list. The number list can hold up to 64
numbers, see [Pw N?].
Sending any command (or only the password [Pw]) will stop the emission. Sending
[Pw A Off] will stop the
emission and the JAS (siren or else), if used with
output timed or On. See JAS
The Alarm function is standby
when A=Off, and is in watch when A=On or
A=O+ as
shown in the status-SMS. Use [Pw A?]
for infos.
The Alarm function can be switched On manually with Input AE (A0) T17
to GND or
Off when
T17 is left open. Command [Pw
A On]
or [Pw A Off] via SMS command
to the controller can be mixed
with the
manual setting. Command [Pw A O+]
will prevent the alarm to be set off with the manual switch.
The JAR function can automatically switch an output relais according to
the Alarm mode On/O+ or Off. See J?
A received ALARM SMS message look like;
!ALARM!
BACKDOOR Alarm
message show !ALARM! first!
A2=Low(0)
TRIGGER!
Or
High(1)
Delayed
SSS sec.
Corresponding input delay. See AL
i0-7:
11011111
Alarm Inputs Level.
Pw S, AL, J?,
M? Suggested
commands.
JAS 8 0 R4
N0 Possibly; JAS that
triggers on alarms.
Alarm
SMS count
Default 5; see parameter D?.
13:02
Controller time
Command [0000 AL] will make SMS you the
actual input delays list and names.
0=9
EXIT!
Delay when manually switched On
1=3
A1
2=4 BACKDOOR
Actual input name
3=1
A3
Only to
number 3 in list
4=0 A4 No alarm on A4 (0!)
5=-553 A5 Was 32, but disabled for 10mn
6=R6=6 A6
Can also be used as an Output
7=1
SOS (your SOS msg)
15c only shown with AL
A=ON M0
04:41
Clock time is added in
most SMS
Possibly, A1 to A6 can
make send only one SMS alarm N1 to N6
programmed
numbers on alarm event if corresponding A1 to A6 delay is set to 1.
Like A3 here above, that will send only one SMS to the number
programmed at
N3 or to the first next valid number in list if no number is found at
the pointed position.
Listing the delays will show the time left for the disabled
input(s). When 0 again, previously programmed input(s) delays will be
reloaded and alarm can be triggered after that.
Command [Pw A5 -600] will
disable
the alarm input for 10nm. Command [Pw
A0
-3600] all Alarm inputs for 1 hour. Negative timing can be from
-32000 seconds to -1, which is about 9 hours.
R Outputs R1 to
R5. Command
[Pw r?] gives details on the output
function.
The five power outputs let you remotely drive any machine or high power
equipment
with a simple SMS command . Output 1, 2 and 3 are (No/NC) and Output 4
and 5
are (NC/NO/NC). Up to 10A 250VAC 2500W can be switched*. Be careful
when
connecting high voltage on the output!
Timing up to 65500 seconds (about 18 Hours) can be added to the
command. No
timing (just: On) will make the output simply switch On until an
Off-command
arrives.
To switch an Output On or Off, send command [Pw
R1 on] or [Pw R2 off].
Multiple commands are supported in the same SMS command to the
controller; [Pw R2 on R3 off R1
On 5 R4 120 s]. Optional trailing s will make the controller
immediately send back an SMS that
will show
the new outputs status including timings.
To switch an output Relais On for 3mn,
send command [Pw R1 on 180].
To do so for 1 hour [Pw R1 3600].
Outputs can be given a meaningful name such as Pump, Light, Motor...
You can
Edit the Output as you like.
So if Relais R1 is Edited to Pump, command
[Pw Pump 600] will switch the
pump for 10min. [Pw Pump Off]
could stop the pump anyway, also
before those 10mns. (See E , editing the In- and Outputs for details).
Some output listing in a [Pw s] status SMS command;
R1 ON 187 Jn 187s before Off after [Pw R1 351].A6 and A7 can also be
used as Low power digital outputs having 0 volt level when Off and
about +4.5V when On. R6 and/or R7 will show up in the status message
when in use and corresponding Alarm inputs are then disabled. Junction
Ji6 and Ji7 remain functional and, if setup, will react on R6 and/or R7
output change.
To use them as output, just send same command as for the other Relais
output. So [R6 on] , [R6 Off] , [R7 30] , [R7 Off] will make them change level and as outputs be able to
source or sink about 3 mA; enough to drive a LED or a NPN power input.
R6 and R7 will become inputs again by writing corresponding Alarm
delay to any value like [A6 64]
, [A7 1]. See A? and AL for
info's on Alarm inputs.
*DANGER: Great care is
recommended when
blindly switching any machine or device remotely. Furthermore, the
switching
order, that normally should arrive in a few seconds, could arrive
delayed at
the controller due to a GSM network overload or any other possible
unexpected reasons. Therefore and in general, you must really know what
you do
and always disconnect the controller outputs and power before doing any
work
or
maintenance on the connected devices.
E EA
Editing the Alarm Inputs A0-A7
To Edit Input A2 into Backdoor, send command [Pw
EA2 Backdoor] to the controller. An alarm SMS triggered by A2 will
then
show;
PUMP
OFF
LIGHT ON 320
NewName OFF
etc........
After editing, the
Alias will be used to command any switching on the
outputs. So
chose short, meaningful and easy-to-remember output names. To switch On
the pump
for 15 minutes and the light for 1H, send command [Pw
Pump 900 Light 3600].
To rename an Ouput or Intput already, the default name will allways be
used. So [Pw
ER1 Motor-2] will rename it from PUMP to MOTOR-2.
M Monitor audio. Send [Pw M?] explains the function.
A Microphone
(delivered) can be connected to terminals 49
(positive, red), 50 (negative,
black) . So put a device On remotely with as example; [Pw R4 On M2 s] to the controller.
After this you can normally voice-call
the
controller and after 2 rings you will be able to listen (optional
trailling (s)
will here add a status message to the command). Values 1 to 5
are
valid, but rather use 2 or 3.
Just hang up to terminate the call, call another time or disable the
monitoring by sending [Pw M0]
or [Pw M9] when finished
because the
SIM could be called from anywhere by anyone else. Mic disable itself at
HH:59+1. [Pw s] or [Pw M?] show the actual setting.
A small speaker 16 to
50 Ohm 0.5W can
also be plugged at T51 T52 for duplex audio. Do not install the speaker
next to the Microphone and install the antenna
as far as possible from the MIC. Any
amplifier can be used to amplify the speaker's output
signal but, an audio transformer (mandatory) needs to be connected in
between to
be
sure of a correct galvanic insulation. To speek trough the amplifier
just use same way as for the mic even when no mic is used. Set M to 2
and call the sim.
Any mistake on these MIC and SP
input/output and the gsm radio module will definitively become out of duty! Same for all other in- or
controller outputs that you may connect at your risk.
M set to 9, [Pw M9] makes the
controller send back a Status short
message when
called.
Message is sent to the first number in the list (position N1) after two
rings. To get the status message, when M9, just
normally (voice) call the controller SIM number. The call can be
terminated when the third ring is heard.
F Factory parameters
restore.
[Pw f?] to the controller
shows the
details.
In case of a major problem, sending [Pw
FSRA] to the controller will force the restoring of the controller
and the
Parameters to the default factory settings. Wait 30 seconds and use
Password
0000 (4 x zero) after a FSRA command. Then
start to
re-program the parameters to the wanted values. Restoring the
controller
and the
Parameters to the default factory settings can also be achieved with
the internal "In Pw
=0000" jumper.
[Pw
Fz]
only
initializes/restarts the built-in radio module (the one that connects
to the
GSM network), password and parameters remains the same. This
action has
the same effect (but from a distance) as removing and re-establishing
the
controller power.
[Pw Fg]
restore the radio module default settings (only use after changing some
AT settings).
The [Pw
F?]
command
to the controller will send back an SMS that also shows others relevant parameters.
D Dial to n numbers for
Alarm and
SOS. [Pw d?] Shows
details +
actual values.
Programming how many numbers will receive the message for SOS and
ALARM. Parameter
Dial tells to how many numbers in thet the Alarm SMS are sent.
Command [Pw D 2 5 d?] will
make the
controller send SOS Alarm SMS to the 2 first numbers found in the
numbers
list and
Alarm-SMS to the 5 first numbers found in the same number list. Numbers
found
at lower position will be served first. Following/trailing d?
optionally
returns you the new settings. (See N above to program the
numbers).
J Junctions.
Ji1-7 Ar,As, Ac, L1, L2, L3, JV1, JV2,
JT1, JT2 JGL, JYg,,,
The "Junctions" functions gives you the possibility to link any
input(s) or any event (Voltage, Temperature, Level changes and others)
to any
output(s) or action. These Junctions, soft
but physical, add
"extended" functionality and flexibility to the controller.
The most simple one for example, can switch an output relais
On, Off or for a time lapse, depending on an input change, while others
can
force an action at measured values programmable edges.
[Pw J?] explains the
principles, [Pw J??] shows
more, [Pw JL] lists the
active Junction parameters,
[Pw Js]
lists
the junction input delays for Ji1 to JL3, [Pw Jm] the unlock parameter for JAC
to JYG and [Pw JLs]
returns a list of basic Jnn settings just for remembering.
A short 5 fields
SMS; [Jnn F1
F2 F3 F4] sent
to the
controller configures a Junction.
Field Jnn is the Junction name like; Ji4 JAC JL2 JYg
Field F1
tells what to do for the outputs for level; 1(i1-7), On(Ar,s,c + L1,2,3), and High(V,T1,2,G,Y).
Field F2 for level; 0 (i1-7), Off (Ar,s,c + L1,2,3) and Low for
(V,T1,2,G,Y).
Field F3 tells which output will eventually be switched.
Field F4 tells at which number the Warning
message will
be
sent.
[Pw
JL] lists the
active Junction and
parameters (listed values are fields examples).
Ji1-7. For example, this simple Junction SMS
command [Pw Ji3 1 0 4 2] to
the controller
makes
switch output R4 On when input i/A 3
changes from
low to high and switches it Off when high to low (to GND) level again.
A warning message is sent to number 2 from list.
From Ji1 to
JL3, F1 what
to do with the Output when the
Input is or goes to High(1) and/or ON level and F2 what
to do when the Input is or becomes low(0) or Off level. (we can
speek of On(1)/Off(0) level for JAR to JL3).
The wanted
output can be switched On, Off, switched for a time lapse or left
unchanged for
corresponding
event. From Ji1 to JL3, each input has its own
configurable delay JnnS for HIGH(Low to
High change)
and LOW(High to Low change) level events to be awaited for before
action
occurs.
[Pw JAR 1 0 2 0] Makes output
Rn automatically switch Output R2 On when
the alarm
function is activated (On) and Off for the opposite. This can command
other
devices On/Off together with the Alarm mode. (As usual, one (1) blank
space character
should separate the command fields).
[Pw JAS 120 -1 5 0] will
force Relais output 5 to be switched on
for wanted time lapse (2mn
here) in case an Alarm event triggers On an alarm input when the alarm
function is On or O+. So a lamp,
siren or other
could be connected to this 10A Relais
output.
[Pw JAC 0 1 3 3]
Configures a Junction for the AC grid power failure/recovery (via the
delivered
AC adaptor connected on T29-30). Relais
output 3 is
set On on grid power cut event and
switched Off on
power recovery. SMS warning is sent to number 3 in list.
JAC to JL3 also have
configurable input delays for both ON/OFF Inputs level
changes. Delay are programmed in SECOND.
So
for example, according to the JAC settings just above, we could
send command [Pw JACS
60 10] to setup a 10s delay to wait
for before
switching R3 On in case of AC power Off and wait 1mn before switching
Off
after AC
power ON recovery.
[Pw
JS]
lists
the junction input delays for i/A1 to i/A7 and JAC to JL3.
A Junction Warning message looks like;
w) Ph,L2
ON! Shows
that power is on at L2(T36)
JUNCTION TRIGGER! Specify
JUNCTION trigger!
to N44
JL2 5 10 3 44 Actual
JL2
junction settings
JL2S 10 20
Jl2 delays On/OFF
(optional)
JL2M 0
Optionel
Mn delays that reforce JL2
R3=ON
Shows what happened with the switching
for: 5s
For how long if it had a timing value
Use Pw
s,
J?, JL Suggests commands that
can be sent
07:10
Controller time at warning.
V
Voltage Alert and setup for V1 and V2.
The voltmeter function can automatically send you a Alert SMS when
exceeding
lower or higher programmed limits. A Low/High Voltage
Alert is programmable
with a single SMS command; [Pw
V1
11.2 13.4] See JV1 and JV2 for any switching and Warnings at
Voltage values.
Voltage V1 will
reflect the battery supply voltage at Terminal (T31). Normally a
battery or else from 8 to 16Vdc maxi can be connected to also feed the
controller via this supply input.The other supply input is the
240/12VDC adaptor. V2 will be externally connected at
(T33),
that can measure from 0 to over 100Vdc. Keep this input lower than 150V to prevent
any problems!
T
Temperature Alert and setup for
T1
and T2.
The thermometer function can automatically send you an Alert when
exceeding lower or higher programmed limits. A Low/High Temperature Alert
is programmable with a single SMS command; [Pw
T1
18.4 19.8].
Command [Pw T1N 22] will send a second Alert
to number 22 from the numbers list when T1 <> are exceeded.
See JT1 and JT2 for any
switching and Alert at
Temperature values.
For a backup
generator, Junction JAC can monitor the AC main grid trough the
adaptor connected to
supply Terminal
T29+ and T30- making possible to automatically start
the generator after grid
failure and stop after grid recovery. Both start/stop can occur
after a
configurable delay from 0 to over 4mn.
When
the adaptor is controlling the main AC grid, we can use another adapter
plugged into the backup
generator
outlet and
connect it to L1, L2 or L3 and so if
wanted also get a warning when the generator give power. We also can use the
optional 380 to 3x8VDC
adaptor that will be connected to the controller RST (L1, L2, L3) inputs. See RST
below...
JAC, JL1, JL2 and JL3 have
identical functionality but only JAC can feed the controller so the
controller will also need to be powered via the 12V Bat inputs T31+ and
T32-. Here also, advantage will be made using fontion V1 to
monitor the generator batterie and possibly JV1.
For a generator
control, any input i/A1-i/A6 can be used for oil and
other
control (see Ji1-Ji6) while output Relais Rn can start and/or stop the engine. In fact,
the
controller has enough possibilities for a full generator set control
and no
other hardware needs to be added.
The controller power supply will need about 30mA in standby mode (A On
or A Off,
with Relais Off) but sometimes current
pulses upto 1 Ampère
when transmitting. So
only adequate power supply should be connected (the delivered
stabilized
adaptor!). If On,
an output Relais take
about 20mA.
Y Humidity sensor Alert and setup (on
T47)
A humidity sensor can optionnally be
connected to
T46(-), 47(s(, 48(+) and 49(s) without mistake
or with
its plug. Always
see the connection schema before
adding or removing any wire from/to the controller. The top label of the delivered device will show
the connections.
This digital sensor provides very
accurate reading
from 0.1 to 100 %. The same sensor also includes a digital thermometer
that
can
measure temperatures from -40 to +125°C at 0,4°C accuracy. T2
connections can
also receive another standard thermometer the same as the delivered
0-95 degrees
sensor.
When the sensor is connected, the function
Yg is activated as soon as the parameters are programmed. Send [Pw
Y?] for infos.
A Low/High humidity Alert
can be programmed with [Pw
Yg 42 68]. Command
[Pw YgN 45] could make send a
second Alert to number 45 when YG <> programmed edges are
exceeded. See also
above the JYG junction
function for switching output at Low//High values and Warning to any
chosen
number.
RST 3 phases main/generator
control and Warnings Use JL1, L2, L3
An effective phases control can be achieved using the optional RST
adapter,
that will transform 380VAC to about 8Vdc, by connecting it to terminals
T35, T36
and T37. Junction L1, L2, L3 can be setup for loss of power on any of
the phase
inputs. A Status SMS will
show RST when power on the 3 Ph or R0T, 0RT
or other
combinations (0 = no power on this input).
When not used as 3PH control, one or more of these inputs R, S and T
can be used
to watch any high tension in the same way as with the delivered
adapter that feeding the
controller from the grid (at T29),
and Junction JAC. We can
deliver
those adapters as well. However, a low voltage input on any of these 3
terminals, from 6 to 24Vdc, is also suitable for the same purpose. See
JL1, JL2,
JL3 junctions for switching actions and warnings on any changes on
these inputs.
C
Run time counter and Totalizator.
Info's with [Pw
C?]
A daily run time counter and totalizator,
that can be
virtually "connected" to one of the inputs i1 to i7 or An, Ln, Vn, Tn,
G or Y, is available.
Count will occur on a defined input level. For example, if L1 is
setup as
the counter input, count happens as long as L1 is powered. If no power,
it will
stop and will count again when re-powered. Count is accurate on the
minute. Status
(if CJ+) and infos SMS [Pw
C?] show the daily counts 0-24H and the totalizator.
Command [0000 Cj 11] for
example will internally connect the run time counter to input L1.
Number 11 here is simply refer
to the junction number. So choosed inputs can be; A1(1) à A7(7),
AC(10),
L1/2/3(11/12/13), V1/2(14/15),
T1/2(16/17), G(18), Y(19).
Status (if CJ+) and infos SMS [Pw C?] show the daily counts 0-24H and the totalizator.
Pw Cj 12
Actual input (L2)
for
counter Cj
Cj;
1-19 Possible Cj inputs
Cd
03:09 CJ
count for this day
CT
56:52 CJ TOTAL count
XXXXX:XX
Cjz
0 Tot=0:00
with [Pw CJz] or [Pw CJz 250]
Pw Cp 6
Actual input for counter Cp
Cp;
3,6 Possible Pulses counter inputs
Pd 0
Cp count for this day
PT -1
Cp TOTAL count
XXXXXXXXXX
Cpz Total ZERO! Total=0
with Command [Pw Cpz]
CpS
5 Input for pulses
decounting, 0 or 5
Cj- Cp- [Pw Cj+] [Pw Cp+] add to status.
When chosen for the run time counter, Cj inputs i/A2, i/A4, i/A6, L1, L2, V1, V2, T1,
T2, Gl
and Yg will count when the input shows a High or On level (when
12Vdc power is on L1 for example)
Inputs i/A1,
i/A3, i/A5, i/A7 and L3 will count for low level or OFF.
Pulse Counter and
Pulse totalizator. A
daily
pulses counter and totalizator can be
setup for input
i/A6 (pulse to GND) or L3 (voltage pulse +8 to +24V).
[Pw Cp 3] [Pw
Cp 6] Pulses are added to the daily pulses counter and added
to the totalizator at 29:59+1. [Pw Cps 5]
makes that other pulses at input i/A5 will be substracted from the
daily
pulses counter
and subsequently
from the pulses totalizator also at 29:59+1.
Fast configuration of one or several controllers can be done using our free
Windows PC
program. Testing will be very easy, because SMS and PC
traffic/commands
can be
used simultaneously. Prog
interface Download, save, unzip and install...
The PC can do all the same that can be done with SMS, but simply
with a few
mouse
clicks from the command list. As before, also a firmware update can be
loaded
into the controller via the program. Any added custom functions are
also
available on request.
Three interface systems (hardware dependent) between controller and PC
are
available; Jumper J+5 need
to be shorted (=put the jumper in) in order to communicate
with the controller. If no comm are in use (or when finished), J+5
Jumper may be removed to save power.
- RS232 TTL level (requires our special
interface cable, same as previous controller types).
- RS232 (requires our or an USB-B/RS232 cable).
- USB (requires a free driver for PC/laptop and one A/B USB cable).